Wall reader (bus) DoorLock-WA7-V2 – MANUAL

Datasheet KXC-WA7-IPx-V2

Overview

Kentix IP wall readers enable contactless control of doors with a MIFARE® DESFire® RFID chip. The wall reader is suitable for installation in intercom systems or behind front panels. The reader’s electronics are housed in a 23 mm high casing. The setup always consists of the actual wall reader and the connected Kentix AccessManager. The wall reader is connected to the AccessManager via a 4-wire connection. The AccessManager itself connects directly to a Power over Ethernet (PoE) capable network switch. To control electric strikes/motor locks, the SmartRelay offers two relay outputs and, depending on the power class of the strikes, an integrated PoE splitter with 24VDC output.

For the operation of the wall readers (version: V2), a Kentix AccessManager for cable readers (KXP-2-RS) with a KentixONE software version of 8.2.0 or higher is required. Information about the relay and circuit diagrams including examples can be found here: AccessManager (Bus)

Safety instructions

Installation
Installation and commissioning may only be carried out by trained specialist personnel in accordance with the instructions.
No modifications of any kind, other than those described in an appropriate manual, are permitted to Kentix GmbH products.
Certain levels of protection must be provided when installing Kentix equipment.
Observe the relevant regulations for installations in the respective environment.
Only operate the products within the defined temperature range.
The instructions should be passed on to the user by the person carrying out the installation.
Kentix accepts no liability for damage to the equipment or components resulting from incorrect installation. No liability is accepted for incorrectly programmed units.
Kentix shall not be liable in the event of malfunctions, damage to property or other damage.
Use of the products, transport and storage
Protect the device during transport, storage and operation from
Protect moisture, dirt and damage.
Battery powered products
Do not use products in potentially explosive atmospheres.
Only operate the products within the defined temperature range.
Installation and battery replacement may only be carried out by trained personnel in accordance with the instructions.
Do not charge, short circuit, open or heat batteries.
When inserting the batteries, pay attention to the correct polarity.
The devices must always be operated with the batteries intended for the product.
When changing batteries, always replace all batteries.
Dispose of old or used batteries properly.
Keep batteries out of the reach of children.
Maintenance
Kentix devices must be checked for functionality as part of annual maintenance.
Disposal
Electrical appliances and batteries must be disposed of separately from household waste.

Controls

  1. Connection terminal
  2. DIP switch

Connection terminal

Clamp #
Readers
Function
Readers
Clamp #
AccessManager
1
2
3RS-485 A6 (BUS A)
4RS-485 B5 (BUS B)
5
6
712 – 30 VDC (+)3 (+)
8GND (-)4 (-)
KXC-WA7-IPx-V2 Connection terminal

DIP switch

DIPFunctionStandard
Settings
1
2
3
4
5RS-485 BIAS ON/OFFOFF
6
7
8Termination 120 Ohm
(terminating resistor)
OFF
KXC-WA7-IPx-V2 DIP switch

Important! Wall readers of different versions (V1, V2 ) cannot be operated on one AccessManager. The version identifier (e.g. V2) is coded in the article number.
For the operation of the wall readers with version 2 (V2), the connected AccessManagers requires at least the KentixONE version 8.2.0

Dimensions

Connection example

The connection example schematically shows the wiring of two DoorLock-WA7 with door contacts and external electric strikes to an AccessManager.

Terminal 2 on the AccessManager provides communication via the data bus and the supply of operating voltage for the wall readers. (terminals 3-6). Terminal 2 serves as a common potential for the power supply of door openers with the PoE supply voltage of the AccessManager.

Terminal 1 is used for connection of potential-free contacts (“door contacts”, terminals 1-4) and switching of door openers by relay 2 (5-6) and relay 1 (7-8). Relay 1 and 2 switch terminal 1 to terminal 2 to common potential (terminal2, terminal 2).

Commissioning of two wall readers on one AccessManager
If two wall readers are to be operated with one AccessManager, proceed as follows for commissioning:
Connect the first wall reader to the AccessManager. Add it in the main device with “DoorLock (IP)”. Only when the first wall reader has been put into operation, they connect the second device and add it as well.

Installation example

  1. Front panel (maximum thickness 5mm)
  2. DoorLock-WA7

The DoorLock-WA7 can be mounted in intercom systems or behind front panels using the adhesive pads supplied. The reading range of the DoorLock depends on the material of the front panel and other environmental influences. The material thickness of the front panel must not exceed 5 mm.

Signaling

FunctionSignal and explanation
Wall reader is offlineLED flashes magenta
Access grantedshort tone, LED flashes green
Door is opened by time profilesLED lights up permanently green
Access deniedshort tone, LED flashes red
Zone is armed3 long tones, simultaneously LED flashes 3x red
Arming not possiblelong tone, LED flashes red
Table signaling