Function | Intelligent power distribution for IT server racks in horizontal design with 3 height units |
ART | KPMDU-RC-2400C13C19-3-32-H KPMDU-RC-2002C13C19-3-32-H KPMDU-RC-2400C13C19-3-16-H KPMDU-RC-2002C13C19-3-16-H |
Rated power, voltage | 11kVA, 230V |
Connector plug | CEE plug (RED) according to IEC60309, 5-pole, 16/32A/230V |
Connection cable | Length 3m, rubber sheathed cable H07RN-F-5G6 (32A) Length 3m, rubber sheathed cable H07RN-F-5G4 (16A) |
Sockets C13 (IEC60320) | 24 (20) |
Sockets C19 (IEC60320) | (2) |
Locking sockets | IEC-LOCK for C13/C19 |
Fuse circuit breaker | 3 x 16A C-type, 6kA short circuit current (32A connection) 3 x 10A C-type, 6kA short circuit current (16A connection) |
Current measurement (calibrated) | Integrated, calibrated current measurement, accuracy Class B (MID, EN 50470-3), minimum current 250mA, maximum current 32A |
Residual current measurement (RCM) | Integrated AC/DC sensitive differential current measurement according to IEC 60664-1, ±300mA/100mA (RMS), accuracy <0.2mA Frequency range DC 0..2kHz |
Connectivity | Ethernet (10/100MBit), PoE Class 3 |
Kentix system socket (Type B) | RJ45 with Kentix specific pinout for system expansion 2 x Digital Input (e.g. door contacts, ext. alarms) 1 x System BUS |
Communication and security | HTTPS (certificate), integrated web server, ReSt API Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS, MODBUS-TCP |
Management | Main satellite management via KentixONE |
Measurement/communication objects | Voltage (V) L1/L2/L3/Total Current (A) L1/L2/L3/Total Consumption (kWh) L1/L2/L3/Total Active power (W) L1/L2L3/total Apparent power (VA) L1/L2/L3/total Reactive power (VAR) L1/L2/L3/Total Effective factor (cos phi) Frequency (Hz) Phase monitoring L1/L2/L3 Differential current AC Differential current DC Fuse status L1/L2/L3 Temperature (°C) Relative humidity (%) Dew point (°C) Vibration (G) Air quality VOC (AIQ Index) |
Display (LCD) | Illuminated LCD display (power, current, voltage, consumption) |
Optical signaling | LED with RED/GREEN (operation, alarm/error status) |
Acoustic signaling | Signal generator with 80dB, 2.3kHz (alarm/fault conditions) |
Factory reset | Button for factory reset(default IP: 192.168.100.226) |
Power dissipation | max. 20W (full load) |
Housing | Sheet metal, powder coated RAL9005, protection class 1 Protection class IP20 |
Size | Height 3U (height units) 483 x 132.5 x 88 mm (WxHxD) |
Weight | approx. 7kg |
Environmental conditions | 0°C to 60°C, humidity 5-95%, non-condensing Storage temperature: -20°C to 60°C |
Certification | CE (2014/30/EC, 2014/35/EC, 2011/65/EU) |
Electrical safety | DGUV-V3 testing, VDE 0105-100 |
Marking | Serial number (barcode) |
Scope of delivery | SmartPDU with connection cable 3m and plug, test protocol |