| Types | KPMDU-xx-xx-xx-1818-3-32-V | KPMDU-xx-xx-xx-1818-3-16-V | KPMDU-xx-xx-xx-1818-1-32-V |
|---|---|---|---|
| Rated power, voltage | up to 22kVA, 230V | up to 11kVA, 230V | up to 7.3kVA, 230V |
| Connector plug | CEE plug(RED) according to IEC60309, 5-pole, 32A/230/400V | CEE plug(RED) according to IEC60309, 5-pole, 16A/230/400V | CEE plug(blue) to IEC60309, 5-pin, 32A/230V |
| Connection cable | Length 3m, rubber cable H07RN-F-5G6 Cable inlet on PDU can be swiveled ±45° | Length 3m, rubber cable H07RN-F-5G2.5 Cable inlet on PDU can be swiveled ±45° | Length 3m, rubber cable H07RN-F-3G6 Cable inlet on PDU can be swiveled ±45° |
| Sockets C13 (IEC60320) | 18 | 18 | 18 |
| Combined socket outlets Cx (C13, C15, C19, C21 IEC60320) | 18 | 18 | 18 |
| Locking sockets | IEC-LOCK for C13/Cx | ||
| Fuse circuit breaker with hinged cover (rated current, characteristic, short-circuit current) | 6x 16A C-type, 10kA | 6x 10A C-type, 10kA | 6x 16A C-type, 10kA |
| Current measurement (calibrated) | Integrated, calibrated current measurement, accuracy Class B (MID, EN 50470-3) Minimum current 250mA, maximum current 32A | ||
| Residual current measurement (RCM), optional | Integrated AC/DC sensitive residual current measurement in accordance with IEC 60664-1 ±300mA/100mA (RMS), accuracy <0.2mA Frequency range DC 0..2kHz Only in types KPMDU-RC-… integrated | ||
| Combination sockets Cx (C13, C15, C19, C21 IEC60320) switchable, optional | 18, individually switchable (bistable relays) with LED Only in types KPMDU-RC-SW-… integrated | ||
| Overvoltage protection, optional | Modular surge arrester type 2+3, rated discharge impulse current (8/20 µs) 20kA, max. discharge impulse current (8/20 µs) 40kA. Leakage surge current (8/20 µs) 40kA Only integrated in types KPMDU-RC-...-SP-… integrated | ||
| Connectivity | Ethernet (10/100MBit), PoE Class 3 | ||
| Kentix system socket (type B) | RJ45 with Kentix-specific assignment for system extensions 2 x digital input (e.g. door contacts, ext. alarms) 1 x system BUS | ||
| Communication and security | HTTPS (certificate), integrated web server, ReSt-API Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS, MODBUS-TCP | ||
| Management | Main satellite management via KentixONE | ||
| Measurement/communication objects | Voltage (V) L1/L2/L3/Total Current (A) L1/L2/L3/Total Consumption (kWh) L1/L2/L3/Total Active power (W) L1/L2L3/total Apparent power (VA) L1/L2/L3/total Reactive power (VAR) L1/L2/L3/total Power quality harmonics (%) THD U/I – L1/L2/L3 Effective factor (cos phi) Frequency (Hz) Phase monitoring L1/L2/L3 Differential current AC Differential current DC Backup status L1/L2/L3 Temperature (°C) Relative humidity (%) Dew point (°C) Vibration (G) Air quality VOC (AIQ Index) | ||
| Display (LCD) | Illuminated LCD display (power, current, voltage, consumption) | ||
| Optical signaling | LED with RED/GREEN (operation, alarm/error status) | ||
| Acoustic signaling | Signal generator with 80dB, 2.3kHz (alarm/fault conditions) | ||
| Factory state | Button for factory reset (default IP: 192.168.100.226) | ||
| Power dissipation | max. 40W (full load) | ||
| Housing | Sheet metal, powder-coated RAL9005, protection class 1, protection rating IP20, mounting bracket | ||
| Size | 1750 x 55.5 x 63 mm (HxWxD) | ||
| Weight | approx. 8kg | ||
| Environmental conditions | 0°C to 60°C, humidity 5-95%, storage temperature: -20°C to 60°C | ||
| Certification | CE (2014/30/EC, 2014/35/EC, 2011/65/EU) | ||
| Electrical safety | DGUV-V3 testing, VDE 0105-100 | ||
| Marking | Serial number (barcode), additional free marking area on front panel (55x30mm) | ||