  4. I/O module with 8 inputs/8 outputs – DATASHEET
  1. Home
  2. Datasheets
  3. I/O module with 8 inputs/8 outputs – DATASHEET

I/O module with 8 inputs/8 outputs – DATASHEET

Order-Codes:

FunctionExpansion module for up to 8 external alarm or system messages and 8 switching outputs (open collector). Communication is via Ethernet, so the module can be mounted anywhere. The configuration is done in the KentixONE software interface. The module offers easy IP configuration and testing of the inputs without additional software via the integrated web server.
Connection possibilityAlarmManager or SiteManager
ConfigurationIntegr. Web server (HTTP)
Default IP: 192.168.255.1 (Admin/Admin)
ProtocolsModbus communication via IP port: 502 (default)
SecurityID, password and IP filter
Connection terminalsPlug-in screw terminals for cables up to 1mm²
EnterängeDigital inputs for voltage switching
ON: +10-50VDC, OFF: +4DC
Input impedance: 10kOHM, overvoltage protection 70VDC
OutputängeOpen collector outputs 10-40VDC
Load capacity 650mA (up to 1.1A overcurrent protection)
Overvoltage protection 47VDC
Alarm output assignmentängeDO1-DO8: Assignment via KentixONE interface
InsulationEthernet 1.5kVDC, I/O 3.7kVrms
EnvironmentOperating temperature 0°C to +45°C, Rel. Humidity 10-90%
NetworkLAN 10/100 Base-TX
Power supplyExternal power supply 12-30VDC, 4.5Watt
Housing72 x 123 x 35 mm (DIN rail mounting)
Scope of deliveryKIO7052, 3m patch cable, power connection cable, manual
ApprovalCE

This module requires an external voltage for input switching. Potential-free contacts must be connected with an external voltage (external power supply with 12-24VDC).

Terminal assignment

Wiring inputs

Wiring outputs