Order-Codes:
FunctionThe extension module enables the connection of up to 8 external alarm or system messages and 8 switching outputs (open collector). As communication takes place via Ethernet, the module can be installed anywhere. Configuration is carried out via the KentixONE software interface. Via the integrated web server, the module offers simple IP configuration and testing of the inputs without the need for additional software.
Connection optionsöpossibilityLog4J
ConfigurationIntegr. Web server (HTTP)
Default IP: 192.168.255.1 (Admin/Admin)
ProtocolsModbus communication via IP port: 502 (default)
SecurityID, password and IP filter
Connection terminalsPlug-in screw terminals for cables up to 1mm²
EnterängeDigital inputs for voltage switching
ON: +10-50VDC, OFF: +4DC
Input impedance: 10kOHM, overvoltage protection 70VDC
OutputängeOpen collector outputs 10-40VDC
Load capacity 650mA (up to 1.1A overcurrent protection)
Overvoltage protection 47VDC
Alarm output assignmentängeDO1-DO8: Assignment via KentixONE interface
InsulationEthernet 1.5kVDC, I/O 3.7kVrms
EnvironmentOperating temperature -20°C to +60°C, Rel. Humidity 10-90%
NetworkLAN 10/100 Base-TX
Power supplyPoE (Class 2) or external power supply 12-30VDC, 4.5Watt
Goäuse72 x 123 x 35 mm (DIN rail mounting)
Scope of deliveryKIO7052, 3m patch cable, power connection cable, manual
CertificationCE

This module requires an external voltage for input switching. Potential-free contacts must be connected to an external voltage (external power supply unit with 12-24VDC).