1. Home
  2. SmartPDU
  3. Datasheets
  4. SmartPDU 40U, 3×16/32A (up to 22kVA) – Datasheet
  1. Home
  2. Datasheets
  3. SmartPDU 40U, 3×16/32A (up to 22kVA) – Datasheet

SmartPDU 40U, 3×16/32A (up to 22kVA) – Datasheet

TypesKPMDU RC-2406C13C19-3-32KPMDU-
RC-4800C13C19-3-32
KPMDU-
RC-2406C13C19-3-16
KPMDU-
RC-4800C13C19-3-16
Rated power, voltageup to 22kVA, 230Vup to 22kVA, 230Vup to 17.9kVA, 230Vup to 13.8kVA, 230V
Connector plugCEE plug(RED) according to IEC60309, 5-pole, 32A/230/400VCEE plug ( RED ) according to IEC60309,
5-pole, 32A/230/400V
CEE plug ( RED ) according to IEC60309,
5-pole, 16A/230/400V
CEE plug ( RED ) according to IEC60309,
5-pole, 16A/230/400V
Connection cableLength 3m, rubber sheathed cable H07RN-F-5G6Length 3m, rubber sheathed cable H07RN-F-5G6Length 3m, rubber cable H07RN-F-5G2.5Length 3m, rubber cable H07RN-F-5G2.5
Sockets C13 (IEC60320)24482448
Sockets C19 (IEC60320)6060
Locking socketsIEC-LOCK for C13/C19
Fuse circuit breaker with hinged cover
(rated current, characteristic, short-circuit current)
3x 10/16A C-type, 6kA
3x 16A C type, 6kA
6x 16A C-type, 6kA3x 10A C type, 6kA
3x 16A C type, 6kA
6x 10A C type, 6kA
Current measurement (calibrated)Integrated, calibrated current measurement, accuracy Class B (MID, EN 50470-3)
Minimum current 250mA, maximum current 32A
Residual current measurement (RCM)Integrated AC/DC sensitive residual current measurement according to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0..2kHz
Type 3 overvoltage protection (optional)Transverse longitudinal voltage protection according to IEC 61643-11
Pluggable protection modules, discharge capacity per pole: In= 5 kA; Imax= 15 kA
Monitored by KentixONE, AC mains form: TN
ART: KPMDU-xxSD-xxxxC13C19-x-x
ConnectivityEthernet (10/100MBit), PoE Class 3
Kentix system socket (type B)RJ45 with Kentix specific pinout for system expansion
2 x digital input (e.g. door contacts, leakage detector, ext. alarms)
1 x System BUS
Communication and securityHTTPS (certificate), integrated web server, ReSt API
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS, MODBUS-TCP
ManagementMain satellite management via KentixONE
Measurement/communication objectsVoltage (V) L1/L2/L3/Total
Current (A) L1/L2/L3/Total
Consumption (kWh) L1/L2/L3/Total
Active power (W) L1/L2L3/total
Apparent power (VA) L1/L2/L3/total
Reactive power (VAR) L1/L2/L3/Total
Effective factor (cos phi)
Frequency (Hz)
Phase monitoring L1/L2/L3
Differential current AC
Differential current DC
Fuse status L1/L2/L3
Temperature (°C)
Relative humidity (%)
Dew point (°C)
Vibration (G)
Air quality VOC (AIQ index)
Display (LCD)Illuminated LCD display (power, current, voltage, consumption)
Optical signalingLED with RED/GREEN (operation, alarm/error status)
Acoustic signalingSignal generator with 80dB, 2.3kHz (alarm/fault conditions)
Factory stateButton for factory reset(default IP: 192.168.100.226)
Power dissipationmax. 40W (full load)
HousingSheet metal, powder coated RAL9005, protection class 1, protection class IP20, mounting bracket can be mounted at a distance of 5U
Size1770 x 78.2 x 62.5 mm (HxWxD)
Weightapprox. 10,5kg
Environmental conditions0°C to 60°C, humidity 5-95%, storage temperature: -20°C to 60°C
CertificationCE (2014/30/EC, 2014/35/EC, 2011/65/EU)
Electrical safetyDGUV-V3 testing, VDE 0105-100
MarkingSerial number (barcode), additional free marking area front panel (60x30mm)
Scope of deliverySmartPDU with connection cable 3m and plug, mounting material: 3 pieces 90° angle bracket,
12 pcs. countersunk head screws M3x15 with hexagon socket 2mm, test report

Was this article helpful?

Related Articles