| Function | MultiSensor for early fire detection and room/area monitoring | 
| Integrated software | KentixONE via integrated web server (HTTPS) | 
| Sensor – air temperature | Measuring range -40 to 85°C (accuracy ± 0.5°C) | 
| Sensor – Relative humidity | Measuring range 0 to 100% (accuracy ±3%) | 
| Sensor – dew point | Calculated in °C | 
| Sensor – surface temperature | 1024 pixel infrared array with germanium glass optics, measuring range -40 to 1,000°C, detection cone depending on type: 40° or 90°, range up to approx. 5m, measurement: temperature image (32×32), movement NETD (Noise Equivalent Temperature Difference): approx. 150mK/1Hz  | 
| Sensor – Vibration | 3-axis accelerometer with position detection (sensitivity adjustable), measuring range 0.25-5G | 
| Sensor – Carbon monoxide (CO) | 0-1,000ppm measurement ± 10%, internal resolution: 20-1,000ppm (0-100%), service life 10 years | 
| Sensor – air quality (VOC, CO2) | Measurement according to IAQ (Index for Air Quality), IAQ value 0-500 according to IAQ table*. | 
| Signal generator | 85dB, 2.3kHz | 
| External alarm inputs (KENTIX system socket)  | 2x alarm input (e.g. armed-active, continuous-active alarm), wiring with potential-free contacts via separate KIO3 IO adapter | 
| External signal outputs (KENTIX system socket)  | 2x signal output (e.g. armed-active alarm, continuous-active alarm), wiring via separate KIO3 IO adapter with relay outputs | 
| LED | ALARM (red), RUN (green), LINK/ACT to LAN socket | 
| Ethernet with PoE | 10/100Mbit (default IP: 192.168.100.222) Power supply via PoE Class 2, power consumption approx. 3W  | 
| Radio (BLE 2.4GHz) (according to version)  | 2.4GHz ISM band (BLE), 128-bit encryption | 
| SD card | Integrated Micro SD card holder as additional memory for image recording, up to 128 GB | 
| SNMP | SNMP V2/3 (write/read), SNMP Traps (Simple Network Management Protocol) | 
| ReST API | ReST API with JSON objects (HTTPS), webhooks | 
| Housing | Material: PS 90 x 90 x 45 mm Weight approx. 100g Colors: White, Black  | 
| Environmental conditions | Temperature 0 – 50°C, humidity 5-95%, non-condensing | 
| Versions | KMS-TI-40-B-BLE (Black housing, 40° optics) KMS-TI-40-W-BLE (White housing, 40° optics) KMS-TI-90-B-BLE (Black housing, 90° optics) KMS-TI-90-W-BLE (White housing, 90° optics) KMS-TI-40-B (black housing, 40° optics) KMS-TI-40-W (white housing, 40° optics) KMS-TI-90-B (black housing, 90° optics) KMS-TI-90-W (white housing, 90° optics)  | 
| Scope of delivery | Mounting bracket, mounting material, SlimLine cable 3m | 
| Accessories | PoE injector (KPOE150S) IO adapter (KIO3) Leakage sensor (KLS03)  | 
| Certification | CE | 
Thermal image sensor field of view
40° optics (ART: KMS-TI-40-x-x)
| Measuring distance | Area | Measuring grid | 
|---|---|---|
| 1m | 73 x 73cm (0,53sqm) | 2,27 x 2,27cm | 
| 2m | 145 x 145cm (2,12sqm) | 4,55 x 4,55cm | 
| 3m | 218 x 218cm (4,55sqm) | 6,82 x 6,82cm | 
| 4m | 291 x 291cm (9,10sqm) | 9,10 x 9,10cm | 
90° optics (ART: KMS-TI-90-x-x)
| Measuring distance | Area | Measuring grid | 
|---|---|---|
| 1m | 200 x 200cm (4,00sqm) | 6,25 x 6,25cm | 
| 2m | 400 x 400cm (16,00sqm) | 12,50 x 12,50cm | 
| 3m | 600 x 600cm (36,00sqm) | 18,75 x 18,75cm | 
| 4m | 800 x 800cm (64,00sqm) | 25,00 x 25,00cm | 
Measurement of air quality according to IAQ Index*
| Air index | Air quality | Effects (long-term exposure) | Proposed measure | 
| 0 – 50 | Excellent | Clean air; the best for the well-being | No measures required | 
| 51 – 100 | Good | No irritation or effects on well-being | No measures required | 
| 101 – 150 | Lightly soiled | Reduction of the well-being possible | Ventilation proposed | 
| 151 – 200 | Moderately dirty | Clearer irritation possible | Increase ventilation with clean air | 
| 201 – 250 | Heavily soiled | Depending on the type of VOCs, exposure can lead to effects such as headaches | Improve ventilation | 
| 251 – 350 | Heavily soiled | More serious health problems possible if harmful VOCs are present | Contamination should be identified when level is reached even without people present; maximize ventilation & reduce presence | 
| > 351 | Extremely dirty | Headache, additional neurotoxic effects possible | Contaminants must be identified; avoid presence in the room and maximize ventilation |