Order-Codes:
FunctionExpansion module for up to 8 external analog inputs. Communication is via Ethernet, so the module can be mounted anywhere. The configuration is done in the KentixONE software interface. The module offers easy IP configuration and testing of the inputs without additional software via the integrated web server.
Connection possibilityAlarmManager or SiteManager
ConfigurationIntegr. Web server (HTTP)
Default IP: 192.168.255.1 (Admin/Admin)
ProtocolsKAM-IO communication via IP port: 502 (default)
SecurityID, password and IP filter
Connection terminalsPlug-in screw terminals for cables up to 1mm²
Enteränge8x differential analog inputs with 16-bit resolution
Sampling rate 10Hz and voltage input 0-10V or current input 4-20mA, accuracy 0.1%.
External sensorsAnalog sensors with:Voltage output 0-10V (default)
Current output 4-20mA (Must be activated by jumper)
Digital outputs: Open Collector (max. 700mA, 5-50 VDC)
Outputs4 digital outputs – not usable
InsulationEthernet 1.5kVDC, I/O 3.7kVrms
EnvironmentOperating temperature 0°C to +45°C, Rel. Humidity 10-90%
NetworkLAN 10/100 Base-TX
Power supplyPoE (Class 1) or external power supply 12-30VDC, 4.3Watt
Housing72 x 123 x 35 mm (DIN rail mounting)
Scope of deliveryKIO7017, 3m patch cable, power connection cable, manual
ApprovalCE
AccessoriesPower supply unit or PoE injector if no PoE supply is available.

Terminal assignment

Circuitry voltage input (0-10V)