Order-Codes:
| Function | Extension module for connecting up to 8 external analog inputs. As communication takes place via Ethernet, the module can be installed anywhere. Configuration is carried out via the KentixONE software interface. Via the integrated web server, the module offers simple IP configuration and testing of the inputs without additional software. |
| Connection optionsöpossibility | Log4J |
| Configuration | Integr. Web server (HTTP) Default IP: 192.168.255.1 (Admin/Admin) |
| Protocols | Modbus communication via IP port: 502 (default) |
| Security | ID, password and IP filter |
| Connection terminals | Plug-in screw terminals for cables up to 1mm² |
| Enteränge | 8x differential analog inputs with 16-bit resolution Sampling rate 10Hz and voltage input 0-10V or current input 4-20mA, accuracy 0.1% |
| External sensors | Analog sensors with: Voltage output 0-10V (default) Current output 4-20mA (must be activated via jumper) Digital outputs: Open collector (max. 700mA, 5-50 VDC) |
| Outputs | 4 digital outputs – not usable |
| Insulation | Ethernet 1.5kVDC, I/O 3.7kVrms |
| Environment | Operating temperature -20°C to +60°C, Rel. Humidity 10-90% |
| Network | LAN 10/100 Base-TX |
| Power supply | PoE (Class 1) or external power supply 12-30VDC, 4.3Watt |
| Goäuse | 72 x 123 x 35 mm (DIN rail mounting) |
| Scope of delivery | KIO7017, 3m patch cable, power connection cable, manual |
| Certification | CE |
| Accessoriesör | Power supply unit or PoE injector if no PoE supply is available. |
Terminal assignment

Circuitry voltage input (0-10V)


Wiring current input (4-20mA)