Extension module (Ethernet)

The extension module (Ethernet) offers the option of integrating external sensors and devices into the KentixONE system. Various versions are available:

DesignationNumber of sensorsNumber of gearshift inputs
KIO70528x digital8x digital
KIO70608x digital8x relay output
KIO705316x digital0
KIO70178x analog4x digital

General

The basic settings for each device include the activation status (on/off) and a name under which all alarms and warnings reported by this device are displayed. This should be as clearly descriptive as possible in order to distinguish the devices.

By selecting the higher-level alarm group, the device is assigned to the system hierarchy.
Alarms are signaled in the higher-level alarm group.

External sensors (digital)

External sensors such as door sounders or leakage sensors can be integrated into KentixONE via the digital inputs.
An external sensor with an active alarm assignment (not “Off”) is displayed as a separate device in the Detail View and therefore also has its own alarm evaluation.
The external sensor is always carried out in the configuration screen of the device to which the sensor is connected.
In the standard configuration, an alarm group cannot be armed if an alarm is pending (so-called forced operation).
If the higher-level alarm group is to be armed even if an alarm is pending for the external sensor, the “Always arm” option must be activated.

NameAPI valueDescription
FromoffThe alarm is deactivated for this input and the status/measured value is not updated.
Sharp-Activearmed-activeIf the higher-level alarm group has been armed, alarms can be triggered. The status/measured value of the input is updated.
Permanently activealways-activeAlarms can be triggered independently of the switching status of the alarm group. The status/measured value of the input is updated.
firefireAlarms can always be triggered. These are reported as fire alarms.
SabotagesabotageAlarms can always be triggered. These are reported as sabotage/intrusion alarms.
System messagesystemAlarms can always be triggered. These are reported as a system message.
Display onlydisplay-onlyNo alarm evaluation takes place. The status/measured value is still updated.
Arming and disarmingarm-disarmThe assigned alarm group can be armed and disarmed via the input.
ArmingpoorThe assigned alarm group can only be armed via the input.
DisarmingdisarmThe assigned alarm group can only be disarmed via the input.

External sensors (analog)

With an analog sensor, the measurement must also be configured for correct evaluation. To do this, the unit to be measured and the measuring range elektrisches Minimum/Maximum (e.g. voltage or current) must be defined and a real equivalent physikalisches Minimum/Maximum (e.g. temperature) must be assigned to these values.

NameAPI valueDescription
FromoffThe alarm is deactivated for this input and the status/measured value is not updated.
Sharp-Activearmed-activeIf the higher-level alarm group has been armed, alarms can be triggered. The status/measured value of the input is updated.
Permanently activealways-activeAlarms can be triggered independently of the switching status of the alarm group. The status/measured value of the input is updated.
firefireAlarms can always be triggered. These are reported as fire alarms.
SabotagesabotageAlarms can always be triggered. These are reported as sabotage/intrusion alarms.
System messagesystemAlarms can always be triggered. These are reported as a system message.
Display onlydisplay-onlyNo alarm evaluation takes place. The status/measured value is still updated.
Arming and disarmingarm-disarmThe assigned alarm group can be armed and disarmed via the input.
ArmingpoorThe assigned alarm group can only be armed via the input.
DisarmingdisarmThe assigned alarm group can only be disarmed via the input.

Switching outputs

The digital switching outputs can be used to control external systems such as sirens, LEDs or locking components (motorized lock, etc.).

The meaning of the alarm assignment differs for switching outputs; in this case, it indicates the function of the switching output or which alarms the output should switch when they occur.

NameAPI valueDescription
Sharp-Activearmed-activeIf an armed-active alarm occurs in the assigned alarm group, the output is switched to high level for the set switching time. An acknowledgement also causes the output to drop back to low level prematurely.
Permanently activealways-activeIf a permanently active alarm occurs in the assigned alarm group, the output is switched to high level for the set switching time. An acknowledgement also causes the output to drop back to low level prematurely.
firefireIf a fire alarm occurs in the assigned alarm group, the output is switched to high level for the set switching time. An acknowledgement also causes the output to drop back to low level prematurely.
SabotagesabotageIf a tamper alarm occurs in the assigned alarm group, the output is switched to high level for the set switching time. An acknowledgement also causes the output to drop back to low level prematurely.
System messagesystemAlarms can always be triggered. These are reported as a system message.
Only for external devices and switching outputs
Collective alarm (group)collected-alarmOutput is switched to high level as long as an alarm is present in the higher-level alarm group. Acknowledgements have no effect.
ManualManuallyCurrently without function
Open doors signalizesignal-open-doorsCurrently without function
Collective alarm armed-active (group)collected-alarm-armed-activeOutput is switched to high level as long as an active alarm is present in the higher-level alarm group.
Collective alarm permanently active (group)collected-alarm-always-activeOutput is switched to high level as long as a permanently active alarm is present in the higher-level alarm group.
Collective fire alarm (group)collected-alarm-fireOutput is switched to high level as long as a fire alarm is present in the higher-level alarm group.
Collective alarm sabotage (group)collected-alarm-sabotageOutput is switched to high level as long as a tamper alarm is present in the higher-level alarm group.