Frontside                            Backside                               Terminal assignment

Voltage Input Differential

Voltage Input Signal Ended

Current Output


Description

Expansion module for connection to the AlarmManager-PRO.

This module extends the external inputs of the AlarmManager on additional 8 analogue alarm inputs. Communication is via Ethernet, so the module can be mounted anywhere. The configuration is done in the software interface of the AlarmManager-PRO. The module provides a build in web-server for simple IP configuration and testing of the inputs and outputs without any additional software.

Connectivity

Analog sensors with:

Voltage output 0-10V (default)

Current output 4-20mA (must be activated by jumper)

Digital outputs:

Open Collector (max. 700mA, 5-50 VDC)

AlarmManager

Connection to Kentix AlarmManager-PRO

Configuration

Integrated Web-Server (HTTP), Default IP: 192.168.255.1 (Admin/Admin)

Protocols

KAM-IO communication through IP port: 502 (Default)

Security

ID, Password and IP-Filter

Terminals

Pluggable screw-terminal for cables up to 1mm²

Inputs

8 differentially analog inputs with 16 bit resolution

Sampling rate 10 Hz and voltage input 0-10V or power input 4-20mA, accuracy 0,1%

Isolation

Ethernet 1,5kVDC, I/O 3,7kVrms

Environment

Operation temperature 0°C to +45°C, Rel. humidity 10-90%

Network

LAN 10/100 Base-TX

Power supply

PoE (Class 1) or external power supply 12-30VDC, 4.3Watt

Chassis

72 x 123 x 35 mm (DIN-rail mounting)

Content of delivery

KIO7017, 3m patch cable, power supply 24VDC, manual

Approvals

CE

Accessories

Power supply or PoE injector if no PoE supply is available