TypeKPMDU-RC-1800C13C19-1–16-H
Nominal power, voltage4.6kVA, 230V
Connector plug2x C20 rubber connector (16A) on backside
Connection cableLength: 2m, rubber hose H07RN-F-2G5
Sockets C13 (IEC60320)18 (2x9) C13 with A+B supply
LockingV-lock for C13 (Z-lock compatible)
Fuse/circuit breaker2x 10A C-type, interlocked
Current measurement

Integrated, calibrated current measurement, accuracy class B (MID, EN 50470-3)
Min. current 250mA, max. current 32A

Residual current measurement (RCM)

Optional

Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0...2kHz

Connectivity

Ethernet (10/100Mbps)
RS485, Modbus RTU

Kentix system socket
  • RJ45 with Kentix specific assignment for system entension
  • 2 x digital input (e.g. door contacts, leakage sensor, external alarms)
  • 2 x digital output (e.g. door locks, signal lamps)
  • 1 x Modbus
Communication and security

HTTPS (certificate), integrated web server, ReSt-API
Port security 802.1x
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP

Management

Management standalone or Kentix PowerManager (KPM-100)
Software deployment (Updates)
Templates for limit values, performance ranges

Measurement and communication objects
  • Voltage (V) L1/L2/L3/total
  • Current (A) L1/L2/L3/total
  • Consumption (kWh) L1/L2/L3/total
  • Active power (W) L1/L2/L3/total
  • Apparent power (VA) L1/L2/L3/total
  • Reactive power (VAR) L1/L2/L3/total
  • Active factor (cos phi)
  • Frequency (Hz)
  • Phase monitoring L1/L2/L3
  • Residual current AC
  • Residual current DC
  • Security status L1/L2/L3
  • Temperature (°C)
  • Relative humidity (%)
  • Dew point (°C)
  • Vibration (G)
Display (LCD)Illuminated LCD display (power, current, voltage, consumption)

Optical signaling

LED red/green (operation, alarm/error states)
Acoustic signalingBuzzer with 80dB, 2.3kHz (alarm/error states)
Factory settingsButton for factory reset in side panel 
ChassisSheet metal, powder-coated RAL9005Appliance class 1, protection class IP20
Dimensions450 x 88 x 120mm (HxWxD)
Weightca. 3.0kg
Environmental conditions-10°C to 55°C, humidity 5-95%Storage temperature: -20°C to 60°C
ApprovalsCE (2014/30/EG, 2014/35/EG, 2011/65/EU)
Electrical securityDGUV V3 Prüfung, VDE 0105-100
MarkingSerial number (bar code)
Content of delivery
  • SmartPDU with cable and plug
  • Inspection protocol