You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 47 Next »


TypeKPMDU-RC-1600C13C19-2–16-H (DUAL PDU)KPMDU-NC-1600C13C19-1–16-H
Nominal power, voltage2x2.3kVA (opt. 2x3.6kVA), 230V1x2.3kVA (opt. 1x3.6kVA), 230V
Connector plug2x C20 mains connector (16A) on backside2x C20 mains connector (16A) on backside
Connection cable

Connection cable needs to be ordered separately

Connection cable needs to be ordered separately
Sockets C13 (IEC60320)18 (2x9) C13 with A+B supply16 (2x8) C13 with A+B supply
LockingIEC-LOCK  for C13
Fuse/circuit breaker2x 10A (opt. 16A) C-type, interlocked
Current measurement

Integrated, calibrated current measurement, accuracy class B (MID, EN 50470-3)
Min. current 250mA, max. current 32A

Residual current measurement (RCM)

Optional

Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0...2kHz

/
Connectivity

Ethernet (10/100Mbps), PoE
Modbus TCP

Kentix system socket
  • RJ45 with Kentix specific assignment for system extension
  • 2 x digital input (e.g. door contacts, leakage sensor, external alarms)
  • 2 x digital output (e.g. door locks, signal lamps)
  • 1 x System BUS
Communication and security

HTTPS (certificate), integrated web server, ReSt-API
Port security 802.1x
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP

Management

Management standalone or Kentix PowerManager (KPM-100)
Software deployment (Updates)
Templates for limit values, performance ranges

Measurement and communication objects
  • Voltage (V) L1/L2/L3/total
  • Current (A) L1/L2/L3/total
  • Consumption (kWh) L1/L2/L3/total
  • Active power (W) L1/L2/L3/total
  • Apparent power (VA) L1/L2/L3/total
  • Reactive power (VAR) L1/L2/L3/total
  • Active factor (cos phi)
  • Frequency (Hz)
  • Phase monitoring L1/L2/L3
  • Residual current AC
  • Residual current DC
  • Security status L1/L2/L3
  • Temperature (°C)
  • Relative humidity (%)
  • Dew point (°C)
  • Vibration (G)
Display (LCD)Illuminated LCD display (power, current, voltage, consumption)

Optical signaling

LED red/green (operation, alarm/error states)
Acoustic signalingBuzzer with 80dB, 2.3kHz (alarm/error states)
Factory settingsButton for factory reset in side panel 
Chassis

Sheet metal, powder-coated RAL9005
Appliance class 1, protection class IP20

Dimensions443 x 88 x 88 mm (HxWxD)
Weightca. 3.0kg
Environmental conditions

-10°C to 55°C, humidity 5-95%
Storage temperature: -20°C to 60°C

Approvals

CE (2014/30/EG, 2014/35/EG, 2011/65/EU)

Electrical security

DGUV-V3 test, VDE 0105-100

MarkingSerial number (bar code)
Content of delivery
  • SmartPDU
  • Inspection protocol