TypeKPMDU-RCSW-2406C13C19-3-32KPMDU-RCSW-2406C13C19-3-16KPMDU-RC-2406C13C19-1-32
Nominal power, voltageup to 17.9kVA (Opt. 22kVA), 230/400Vup to 13.8kVA, 230/400Vup to 7.3kVA, 230V
Connector plugCEE-connector (red) acc. to IEC60309, 5-pole, 32A/230/400VCEE-connector (red) acc. to IEC60309, 5-pole, 32A16A/230/400VCEE-connector (blue) acc. to IEC60309, 1-pole, 32A/230V
Connection cable

Length 3m, rubber hose

H07RN-F-5G6

Length 3m, rubber hose

H07RN-F-5G2,5

Length 3m, rubber hose

H07RN-F-3G6

Sockets C13 (IEC60320)

24, switchable sockets (bistable relays), single metered
Sockets C19 (IEC60320)6, switchable sockets (bistable relays), single metered
Locking of sockets
IEC-LOCK  for C13/C19
Fuse, circuit breaker

3 x 10A C-type 6kA short-circuit current, interlocked (opt. 16A)

3 x 16A C-type 6kA short-circuit current, interlocked

Current measurement per socket
Integrated individual measurement of each socket (U, I, P, W) with reference to the calibrated total measurement
Current measurement total (calibrated)

Integrated, calibrated total current measurement, accuracy class B (MID, EN 50470-3)
Min. current 250mA, max. current 32A

Residual current measurement (RCM)

Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0...2kHz

Connectivity

Ethernet (10/100Mbps)
ModBus TCP

Kentix system socket

RJ45 with Kentix specific assignment for system extension
2 x digital input (e.g. door contacts, leakage detection, external. alarms)

2 x digital output (e.g. door locks, signal lamps)

1 x System BUS

Connection Rack-Lever (Rack Access Control)Connection of two electronic rack levers for access control with RFID/PIN via system socket
Communication and security

HTTPS (certificate), integrated web server
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP

Management

Master-slave administration, SmartPDU or PowerManager configurable as master, up to 100 slaves per master, automatic software deployment

Measurement and communication examples

Voltage (V) L1/L2/L3/total

Current (A) L1/L2/L3/total

Consumption (kWh) L1/L2/L3/total

Active power (W) L1/L2/L3/total

Apparent power (VA) L1/L2/L3/total

Reactive power (VAR) L1/L2/L3/total

Active factor (cos phi)

Frequency (Hz)

Phase monitoring L1/L2/L3

Residual current AC

Residual current DC

Fuse status L1/L2/L3

Temperature (°C)

Relative humidity (%)

Dew point (°C)

Vibration (G)

Pre-Fire detection (Carbon Monoxide CO), optional with additional module

Display (LCD)Illuminated LCD display (power, current, voltage, consumption)
Optical signalingLED red/green (operation, alarm/error states)
Acoustic signalingBuzzer with 80dB, 2.3kHz (alarm/error states)
Factory settingsButton for factory reset in top panel (Default IP: 192.168.100.226)
Power dissipationca. 80W (full load)
ChassisSheet metal, powder-coated RAL9005, protection class 1, protection rating IP20, mounting bracket mountable at a distance of 5HE
Dimensions1770 x 78.2 x 62.5 mm (HxWxD)
Weightapprox. 11.5kg
Environmental conditions10°C up to 55°C, humidity 5-95%, storage temperature: -20°C to 60°C
ApprovalsCE (2014/30/EG, 2011/65/EU)
Electrical securityDGUV-V3 test, VDE 0105-100
MarkingSerial number (barcode), additional free labeling area front plate (60x20mm)
Content of deliverySmartPDU with 3m cable and connector, mounting material: 3 pcs. 90° angle brackets, 12 pcs. countersunk-head screws M3x15 with hexagon socket 2mm, inspection protocol