changes.mady.by.user Johannes Bühner
Saved on Sep 29, 2021
...
Length 3m, rubber hose
H07RN-F-5G6
H07RN-F-5G2,5
H07RN-F-3G6
Sockets C13 (IEC60320)
3 x 10A C-type 6kA short-circuit current, interlocked (opt. 16A)
3 x 16A C-type 6kA short-circuit current, interlocked
Integrated, calibrated total current measurement, accuracy class B (MID, EN 50470-3)Min. current 250mA, max. current 32A
Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1±300mA/100mA (RMS), accuracy <0.2mAFrequency range DC 0...2kHz
Ethernet (10/100Mbps)ModBus TCP
RJ45 with Kentix specific assignment for system extension2 x digital input (e.g. door contacts, leakage detection, external. alarms)
2 x digital output (e.g. door locks, signal lamps)
1 x System BUS
HTTPS (certificate), integrated web serverProtocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP
Master-slave administration, SmartPDU or PowerManager configurable as master, up to 100 slaves per master, automatic software deployment
Voltage (V) L1/L2/L3/total
Current (A) L1/L2/L3/total
Consumption (kWh) L1/L2/L3/total
Active power (W) L1/L2/L3/total
Apparent power (VA) L1/L2/L3/total
Reactive power (VAR) L1/L2/L3/total
Active factor (cos phi)
Frequency (Hz)
Phase monitoring L1/L2/L3
Residual current AC
Residual current DC
Fuse status L1/L2/L3
Temperature (°C)
Relative humidity (%)
Dew point (°C)
Vibration (G)
Pre-Fire detection (Carbon Monoxide CO), optional with additional module