TypesKPMDU-RCSW-4800C13C19-2-16KPMDU-RCSW-4800C13C19-2-32KPMDU-RCSW-4800C13C19-6-16
Rated power, voltageup to 7.3kVA, 230/400Vup to 13.8kVA, 230/400Vup to 13.8kVA, 230/400V
Connector plug2x CEE plug(BLUE) to IEC60309, 3-pin, 16A/230/400V2x CEE plug(BLUE) to IEC60309, 3-pin, 32A/230/400V2x CEE plug(RED) to IEC60309, 5-pin, 16A/230/400V
Connection cable2x length 3m, rubber cableH07RN-F-3G2.52x length 3m, rubber cableH07RN-F-3G62x length 3m, rubber cableH07RN-F-5G2.5
Sockets C13 (IEC60320) switchable, measured 48, individually switchable (bistable relays) with LED48, individually switchable (bistable relays) with LED48, individually switchable (bistable relays) with LED
Locking socketsIEC-LOCK for C13
Fuse circuit breaker6 x 10A C-type, 6kA short circuit current, interlocked6 x 16A C-type, 6kA short-circuit current, interlocked6 x 10A C-type, 6kA short circuit current, interlocked
Current measurement per fuseIntegrated individual measurements of the 6 fuse ranges (U, I, P, W) with reference to the calibrated overall measurement
Current measurement (calibrated)Integrated, calibrated total current measurement with separation according to phases L1/2/3, accuracy Class B (MID, EN 50470-3)
Minimum current 250mA, maximum current 3x32A
Residual current measurement (RCM)Integrated AC/DC sensitive residual current measurement in accordance with IEC 60664-1
±300mA/100mA (RMS), Accuracy <0.2mA
Frequency range DC 0.2kHz
ConnectivityEthernet (10/100MBit), PoE
Modbus TCP
Kentix system socket (type B)RJ45 with Kentix-specific assignment for system extensions
2 x digital input (e.g. door contacts, leakage detector, ext. alarms)
1 x system BUS
Rack locking lever connection (access control)Connection of two electronic rack levers for access control with RFID/PIN via system socket
Communication and securityHTTPS (certificate), integrated web server, ReSt-API
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS
ManagementMaster-slave management, SmartPDU or PowerManager can be configured as master, up to 100 slaves per master, automatic Software Deployment
Measurement/communication objectsVoltage (V) L1/L2/L3/Total
Current (A) L1/L2/L3/Total
Consumption (kWh) L1/L2/L3/Total
Active power (W) L1/L2L3/total
Apparent power (VA) L1/L2/L3/total
Reactive power (VAR) L1/L2/L3/total
Effective factor (cos phi)
Frequency (Hz)
Phase monitoring L1/L2/L3
Differential current AC
Differential current DC
Fuse status L1/L2/L3
Temperature (°C)
Relative humidity (%)
Dew point (°C)
Vibration (G)
Display (LCD)Illuminated LCD display for total measurement (power, current, voltage, consumption)
Optical signalingLED with RED/GREEN (operation, alarm/error status)
Acoustic signalingSignal generator with 80dB, 2.3kHz (alarm/fault conditions)
Factory stateButton for factory reset(default IP: 192.168.100.226)
Power dissipationapprox. 80W (full load)
HousingSheet metal, powder-coated RAL9005, protection class 1, protection rating IP20, mounting bracket can be mounted at 5U intervals
Size1770 x 78.2 x 62.5 mm (HxWxD)
Weightapprox. 11,5kg
Environmental conditions-10°C to 55°C, humidity 5-95%, storage temperature: -20°C to 60°C
ExamsCE (2014/30/EC, 2014/35/EC, 2011/65/EU)
Electrical safetyDGUV-V3 testing, VDE 0105-100
MarkingSerial number (barcode), additional free marking area front panel (60x30mm)