SmartPDU 40HE SWITCHED, 3×16/32A (up to 22kVA) – Datasheet

TypesKPMDU-RCSW-2406C13C19-3-32KPMDU-RCSW-2406C13C19-3-16KPMDU-RCSW-2406C13C19-1-32
Rated power, voltageup to 22kVA, 230/400Vup to 11kVA, 230/400Vup to 7,3kVA, 230V
Connector plugCEE plug(RED) according to IEC60309, 5-pole, 32A/230/400VCEE plug(RED) according to IEC60309, 5-pole, 16A/230/400VCEE plug (BLUE) according to IEC60309, 1-pole, 32A/230V
Connection cableLength 3m, rubber sheathed cableH07RN-F-5G6Length 3m, rubber sheathed cableH07RN-F-5G2,5Length 3m, rubber sheathed cableH07RN-F-3G6
Sockets C13 (IEC60320) switchable, measured24, individually switchable (bistable relays) with LED
Sockets C19 (IEC60320) switchable, measured6, individually switchable (bistable relays) with LED
Locking socketsIEC-LOCK for C13/C19
Fuse circuit breaker3 x 16A C-type, 6kA short-circuit current, interlocked (opt. 10A)
3 x 16A C-type, 6kA short circuit current, interlocked
Current measurement per fuseIntegrated individual measurements of the 6 fuse ranges (U, I, P, W) with reference to the calibrated total measurement
Current measurement (calibrated)Integrated, calibrated total current measurement with separation according to phases L1/2/3, accuracy Class B (MID, EN 50470-3)
Minimum current 250mA, maximum current 3x32A
Residual current measurement (RCM)Integrated AC/DC sensitive residual current measurement according to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0.2kHz
ConnectivityEthernet (10/100MBit), PoE
Modbus TCP
Kentix system socket (type B)RJ45 with Kentix specific pinout for system expansion
2 x digital input (e.g. door contacts, leakage detector, ext. alarms)
1 x System BUS
Connection rack closing lever (access control)Connection of two electronic rack levers for access control with RFID/PIN via system socket
Communication and securityHTTPS (certificate), integrated web server, ReSt API
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS
ManagementMaster-slave management, SmartPDU or PowerManager configurable as master, up to 100 slaves per master, autom. Software Deployment
Measurement/communication objectsVoltage (V) L1/L2/L3/Total
Current (A) L1/L2/L3/Total
Consumption (kWh) L1/L2/L3/Total
Active power (W) L1/L2L3/total
Apparent power (VA) L1/L2/L3/total
Reactive power (VAR) L1/L2/L3/Total
Effective factor (cos phi)
Frequency (Hz)
Phase monitoring L1/L2/L3
Differential current AC
Differential current DC
Fuse status L1/L2/L3
Temperature (°C)
Relative humidity (%)
Dew point (°C)
Vibration (G)
Display (LCD)Illuminated LCD display for total measurement (power, current, voltage, consumption)
Optical signalingLED with RED/GREEN (operation, alarm/error status)
Acoustic signalingSignal generator with 80dB, 2.3kHz (alarm/fault conditions)
Factory stateButton for factory reset(default IP: 192.168.100.226)
Power dissipationapprox. 80W (full load)
HousingSheet metal, powder coated RAL9005, protection class 1, protection class IP20, mounting bracket can be mounted at a distance of 5U
Size1770 x 78.2 x 62.5 mm (HxWxD)
Weightapprox. 11,5kg
Environmental conditions-10°C to 55°C, humidity 5-95%, storage temperature: -20°C to 60°C
ExamsCE (2014/30/EC, 2014/35/EC, 2011/65/EU)
Electrical safetyDGUV-V3 testing, VDE 0105-100
MarkingSerial number (barcode), additional free marking area front panel (60x30mm)
Scope of deliverySmartPDU with connection cable 3m and plug, mounting material: 3 pcs. 90° angle bracket, 12 pcs. countersunk head screws. M3x15 with hexagon socket 2mm, test report