Order-Codes:
FunctionExpansion module for up to 8 external alarm or system messages and 8 switching outputs (open collector). Communication is via Ethernet, so the module can be mounted anywhere. The configuration is done in the KentixONE software interface. The module offers easy IP configuration and testing of the inputs without additional software via the integrated web server.
Connection possibilityAlarmManager or SiteManager
ConfigurationIntegr. Web server (HTTP)
Default IP: 192.168.255.1 (Admin/Admin)
ProtocolsModbus communication via IP port: 502 (default)
SecurityID, password and IP filter
Connection terminalsPlug-in screw terminals for cables up to 1mm²
EnterängeDigital inputs for voltage switching
ON: +10-50VDC, OFF: +4DC
Input impedance: 10kOHM, overvoltage protection 70VDC
OutputängeOpen collector outputs 10-40VDC
Load capacity 650mA (up to 1.1A overcurrent protection)
Overvoltage protection 47VDC
Alarm output assignmentängeDO1-DO8: Assignment via KentixONE interface
InsulationEthernet 1.5kVDC, I/O 3.7kVrms
EnvironmentOperating temperature 0°C to +45°C, Rel. Humidity 10-90%
NetworkLAN 10/100 Base-TX
Power supplyPoE (Class 2) oder externes Netzteil 12-30VDC, 4.5Watt
Housing72 x 123 x 35 mm (DIN rail mounting)
Scope of deliveryKIO7052, 3m patch cable, power connection cable, manual
ZertifizierungCE

Diese Modul benötigt zur Eingangsbeschaltung eine externe Spannung. Potentialfreie Kontakte müssen mit einer äußeren Spannung (Externes Netzteil mit 12-24VDC) belegt werden.

Terminal assignment

Wiring inputs

Wiring outputs