1. Home
  2. SmartPDU
  3. Datasheets
  4. PowerManager – DATASHEET
  1. Home
  2. Datasheets
  3. PowerManager – DATASHEET

PowerManager – DATASHEET

Order-Codes:
FunctionPower management of external electricity meters with Modbus-RTU (RS485) or Modbus-TCP (Ethernet)
Integrated softwareKentixONE via integrated web server (HTTPS)
OperationStand-alone or networked
Quantity counter32 Modbus RTU counter
100 Modbus TCP counter
NetworkingAny number of PowerManager as main satellite
SD cardIntegrated Micro SD card holder up to 128 GB
Acoustic signal generator85dB, 2.3kHz
LEDALARM (red), RUN (green), LINK/ACT to LAN socket
ButtonReset button
Network (PoE)10/100 Mbit Ethernet port with PoE
Power supply (PoE)PoE class 3, power consumption in operation approx. 3W with splitter function max. 15W short term.
Integrated PoE splitterVoltage output 24VDC/500mA (max. 1A/250ms) for connection of reader and door opener
Connection electric strike/lock2x relay: 125VAC/60VDC, 1A, change-over contact (NO/NC) switchable, connection cable thickness: 0.205 – 1.31 mm²
Digital inputs2x Digital inputs, each door configurable as:
– Alarm input (door open monitoring)
– Pushbutton input for door opening
RFID reader connection4-wire cable (cable: J-Y(ST)Y, 4x2x0.8), cable length up to 500m
Dimensions47 x 48 x 33 mm WxHxD
Environmental conditionsTemperature 0 to 60°C, humidity 5-95%, non-condensing
Protection classIP20
Mounting– On mounting rail / top-hat rail (35mm)
– In switch box 60mm
IP Ports– 443 TCP (HTTPS)
– 5222 TCP (KentixONE-GO)
– 161 UDP (SNMP-GET)
– 162 UDP (SNMP-TRAP)
Scope of deliveryAccessManager, mounting material, SlimLine cable 3m
AccessoriesPoE Injector(KPOE150S)
ExamsCE, FCC
Was this article helpful?

Related Articles