Order-Codes:
FunctionBiometric wall reader for surface mounting and 2-factor verification
Connection possibilityDoorLock AccessManager (ART: KXP-2-RS)
ConfigurationAbout KentixONE
RFID Reader 13.56MHzMIFARE® DESFire®
MIFARE® Classic, LEGIC prime
Dimensions88 x 123 x 55 mm WxHxD
LEDRED, GREEN
Acoustic signal generator80dB, 2.3kHz
Connection of wall reader to AccessManager4-wire cable (cable: J-Y(ST)Y, 4x2x0.8)
Cable length up to max. 500m
Addressing
Terminating resistor
Coding switch (default address: 1)
ASSIGNMENT DIP 1:
(1) ADDRESS 1(ON/OFF)
(2) ADDRESS 2 (ON/OFF)
(3) –
(4) –
(5) –
(6) BAUD RATE(ON)
(7) BAUD RATE(OFF)
(8) TERMINATING RESISTOR (ON/OFF)

ASSIGNMENT DIP 2:
(1) TERMINATING RESISTOR (ON/OFF)
(2) –
Communication2-wire RS485, encrypted (AES128)
EnvironmentTemperature -10°C to +55°C
Power supply10-30VDC, power consumption 1.9W
Connection5-pole terminal block detachable
MOVEMENT:
(1) 10-30VDC
(2) GND
(3) DATA-A
(4) DATA-B
(5) –
Protection classIP54
Scope of deliveryWall reader
ExamsCE