Order-Codes:
| Function | Extension module for connecting up to 6 digital inputs and 6 relay outputs |
| Connection optionsöpossibility | Log4J |
| Configuration | Integr. Web server (HTTP) Default IP: 192.168.255.1 |
| Protocols | Modbus TCP / UDP, MQTT, SNMP v2c |
| Security | ID, password and IP filter |
| Connection terminals | Pluggable spring terminals for cables up to 1 mm² |
| Enteränge | Channels: 6 digital inputs Type: potential-free and floating wiring possible Counter function: 32 bit, max. 3 kHz |
| Outputs | Channels: 6 relay outputs Load capacity: 5 A @ 250 VAC / 24 VDC Switching time: max. 10 ms Switch-off time: max. 5 ms Mechanical service life: 2 × 10⁷ switching cycles Electrical service life: 10⁵ switching cycles |
| Alarm output assignmentänge | DO1-DO6: Assignment via KentixONE interface |
| Insulation | I/O isolation: 3000 V DC |
| Environment | Operating temperature: -25 to +75 °C Humidity: 10 to 90 % RH, non-condensing |
| Network | 2x RJ45, LAN 10/100 Base-TX |
| Power supply | PoE (Class 2) or external power supply unit 10-48VDC, 4.4W |
| Goäuse | 33 x 126 x 108 mm (DIN rail mounting) |
| Scope of delivery | KIO2260, 3m patch cable, instructions |
| Certification | CE, RoHS compliant |
| Accessories | Power supply unit or PoE injector if no PoE supply is available |
Terminal assignment

Wiring