You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 39 Next »


Type

KPMDU-RC-1800C13C19-1–16-H

Nominal power, voltage2x2.3kVA (opt. 2x3.6kVA), 230V
Connector plug2x C20 mains connector (16A) on backside
Connection cable

Connection cable needs to be ordered separately

Sockets C13 (IEC60320)18 (2x9) C13 with A+B supply
LockingIEC-LOCK  for C13
Fuse/circuit breaker2x 10A (opt. 16A) C-type, interlocked
Current measurement

Integrated, calibrated current measurement, accuracy class B (MID, EN 50470-3)
Min. current 250mA, max. current 32A

Residual current measurement (RCM)

Optional

Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1
±300mA/100mA (RMS), accuracy <0.2mA
Frequency range DC 0...2kHz

Connectivity

Ethernet (10/100Mbps), PoE
Modbus TCP

Kentix system socket
  • RJ45 with Kentix specific assignment for system extension
  • 2 x digital input (e.g. door contacts, leakage sensor, external alarms)
  • 2 x digital output (e.g. door locks, signal lamps)
  • 1 x System BUS
Communication and security

HTTPS (certificate), integrated web server, ReSt-API
Port security 802.1x
Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP

Management

Management standalone or Kentix PowerManager (KPM-100)
Software deployment (Updates)
Templates for limit values, performance ranges

Measurement and communication objects
  • Voltage (V) L1/L2/L3/total
  • Current (A) L1/L2/L3/total
  • Consumption (kWh) L1/L2/L3/total
  • Active power (W) L1/L2/L3/total
  • Apparent power (VA) L1/L2/L3/total
  • Reactive power (VAR) L1/L2/L3/total
  • Active factor (cos phi)
  • Frequency (Hz)
  • Phase monitoring L1/L2/L3
  • Residual current AC
  • Residual current DC
  • Security status L1/L2/L3
  • Temperature (°C)
  • Relative humidity (%)
  • Dew point (°C)
  • Vibration (G)
Display (LCD)Illuminated LCD display (power, current, voltage, consumption)

Optical signaling

LED red/green (operation, alarm/error states)
Acoustic signalingBuzzer with 80dB, 2.3kHz (alarm/error states)
Factory settingsButton for factory reset in side panel 
Chassis

Sheet metal, powder-coated RAL9005
Appliance class 1, protection class IP20

Dimensions443 x 88 x 88 mm (HxWxD)
Weightca. 3.0kg
Environmental conditions

-10°C to 55°C, humidity 5-95%
Storage temperature: -20°C to 60°C

Approvals

CE (2014/30/EG, 2014/35/EG, 2011/65/EU)

Electrical security

DGUV-V3 test, VDE 0105-100

MarkingSerial number (bar code)
Content of delivery
  • SmartPDU
  • Inspection protocol