Art.-No.: KIO7017, KIO7052, KIO7053 • Datasheet: KIO7017, KIO7052, KIO7053

Factory defaults

Default IP-Adress

192.168.255.1

Subnetz-Mask

255.255.255.0

User

Admin

Password

Admin

The AlarmManager-PRO can be extended with up to 32 IO modules by additional inputs and outputs.

Three external modules are available for this purpose, the differences are shown in the following table:

               


KIO7052

KIO7053KIO7017

Digital inputs 816-
Digital outputs8-4
Analog inputs--8
ProtocolModbus TCP
IP Port502 TCP
Network configuration

Web Server HTTP, Port 80

Default IP: 192.168.255.1 (Admin/Admin)

AlarmManager-PRO configuration

Configuration completely via AlarmManager-PRO

Only IP settings on IO module necessary

Alarm display logic freely adjustable

power supply

PoE

Extern 12-30VDC

AssemblyDIN rail, stackable
Connection variant 1

SINK
Readback as 1
+10 ~ +50VDC

ON Stage
Readback as 0

Potential-free wiring

Voltage Input Differential

Default 0-10V

Connection variant  2

SINK
Readback as 0
OPEN or <4 VDC

OFF Stage
Readback as 1

Potential-free wiring

Voltage Input Single Ended

Default 0-10V

Connection variant 3

SOURCE
Readback as 1
+10 ~ +50 VDC


-

Current Input 4-20mA*

 

Move Jumpers!

Connection variant  4

SOURCE
Readback as 0
OPEN or <4 VDC

--
Connection variant  5

DIGITAL OUTPUT
ON State
Readback as 1

--
Connection variant  6

DIGITAL OUTPUT
OFF State
Readback as 0

--

* To change from voltage measurement 0-10V (default) to current measurement 4-20mA, the jumper inside the module must be changed.

Commissioning and configuration

The modules can be supplied with power either via PoE or via an external power supply unit. When using a power supply unit, be sure to observe the information on the power supply in the data sheet. Information on the wiring of the inputs and outputs can also be found in the data sheet in the appendix.