Type | KPMDU-RC-2406C13C19-3-32 | KPMDU-RC-4800C13C19-3-32 | KPMDU-RC-2406C13C19-1-32 |
Nominal power, voltage | up to 17.9kVA, 230/400V | up to 13.8kVA, 230/400V | up to 7.3kVA, 230V |
Connector plug | CEE-connector (red) acc. to IEC60309, 5-pole, 32A/230/400V | CEE-connector (red) acc. to IEC60309, 5-pole, 32A/230/400V | CEE-connector (blue) acc. to IEC60309, 1-pole, 32A/230V |
Connection cable | Length 3m, rubber hose H07RN-F-5G6 | Length 3m, rubber hose H07RN-F-5G6 | Length 3m, rubber hose H07RN-F-5G6 |
Sockets C13 (IEC60320) | 24 | 48 | 24 |
Sockets C19 (IEC60320) | 6 | 0 | 6 |
Locking | IEC-LOCK for C13/C19 | ||
Fuse, circuit breaker | 3 x 10A C-type 6kA short-circuit current, interlocked 3 x 16A C-type 6kA short-circuit current, interlocked | 6 x 10A C-type 6kA short-circuit current, interlocked | 3 x 10A C-type 6kA short-circuit current, interlocked 3 x 16A C-type 6kA short-circuit current, interlocked |
Current measurement (calibrated) | Integrated, calibrated current measurement, accuracy class B (MID, EN 50470-3) | ||
Residual current measurement (RCM) | Integrated AC/DC sensitive residual current measurement acc. to IEC 60664-1 | ||
Connectivity | Ethernet (10/100Mbps) | ||
Kentix system socket | RJ45 with Kentix specific assignment for system extension 2 x digital output (e.g. door locks, signal lamps) 1 x ModBus RTU | ||
Communication and security | HTTPS (certificate), integrated web server | ||
Management | Master-slave administration, SmartPDU or PowerManager configurable as master, up to 100 slaves per master, automatic software deployment | ||
Measurement and communication examples | Voltage (V) L1/L2/L3/total Current (A) L1/L2/L3/total Consumption (kWh) L1/L2/L3/total Active power (W) L1/L2/L3/total Apparent power (VA) L1/L2/L3/total Reactive power (VAR) L1/L2/L3/total Active factor (cos phi) Frequency (Hz) Phase monitoring L1/L2/L3 Residual current AC Residual current DC Fuse status L1/L2/L3 Temperature (°C) Relative humidity (%) Dew point (°C) Vibration (G) Pre-Fire detection (Carbon Monoxide CO), optional with additional module | ||
Display (LCD) | Illuminated LCD display (power, current, voltage, consumption) | ||
Optical signaling | LED red/green (operation, alarm/error states) | ||
Acoustic signaling | Buzzer with 80dB, 2.3kHz (alarm/error states) | ||
Factory settings | Button for factory reset in top panel (Default IP: 192.168.100.226) | ||
Power dissipation | max. 40W (full load) | ||
Chassis | Sheet metal, powder-coated RAL9005, protection class 1, protection rating IP20, mounting bracket mountable at a distance of 5HE | ||
Dimensions | 1770 x 78.2 x 62.5 mm (HxWxD) | ||
Weight | approx. 10.5kg | ||
Environmental conditions | 10°C up to 55°C, humidity 5-95%, storage temperature: -20°C to 60°C | ||
Approvals | CE (2014/30/EG, 2011/65/EU) | ||
Electrical security | DGUV-V3 test, VDE 0105-100 | ||
Marking | Serial number (barcode), additional free labeling area front plate (60x20mm) | ||
Content of delivery | SmartPDU with 3m cable and connector, mounting material: 3 pcs. 90° angle brackets, 12 pcs. countersunk-head screws M3x15 with hexagon socket 2mm, inspection protocol |