Frontside Backside Terminal assignment
Voltage Input Differential | Voltage Input Signal Ended | Current Output |
Description | Expansion module for connection to the AlarmManager-PRO. This module extends the external inputs of the AlarmManager on additional 8 analogue alarm inputs. Communication is via Ethernet, so the module can be mounted anywhere. The configuration is done in the software interface of the AlarmManager-PRO. The module provides a build in web-server for simple IP configuration and testing of the inputs and outputs without any additional software. |
Connectivity | Analog sensors with: Voltage output 0-10V (default) Current output 4-20mA (must be activated by jumper) Digital outputs: Open Collector (max. 700mA, 5-50 VDC) |
AlarmManager | Connection to Kentix AlarmManager-PRO |
Configuration | Integrated Web-Server (HTTP), Default IP: 192.168.255.1 (Admin/Admin) |
Protocols | KAM-IO communication through IP port: 502 (Default) |
Security | ID, Password and IP-Filter |
Terminals | Pluggable screw-terminal for cables up to 1mm² |
Inputs | 8 differentially analog inputs with 16 bit resolution Sampling rate 10 Hz and voltage input 0-10V or power input 4-20mA, accuracy 0,1% |
Isolation | Ethernet 1,5kVDC, I/O 3,7kVrms |
Environment | Operation temperature 0°C to +45°C, Rel. humidity 10-90% |
Network | LAN 10/100 Base-TX |
Power supply | PoE (Class 1) or external power supply 12-30VDC, 4.3Watt |
Chassis | 72 x 123 x 35 mm (DIN-rail mounting) |
Content of delivery | KIO7017, 3m patch cable, power supply 24VDC, manual |
Approvals | CE |
Accessories | Power supply or PoE injector if no PoE supply is available |