The Kentix leakage sensor KLS03 reports its alarm through the digital input on the AlarmManager or MultiSensor.

Please note that the alarm assignment of system input 1 to the AlarmManager or MultiSensor has to be set permanently active. Otherwise, the leakage sensor won't trigger any alarm at all or only in the armed state.

The alarm assignment can be set in the ControlCenter in the Sensor Devices tab for each individual sensor.

If the leakage sensor is operated on a MultiSensor with the aid of a power adapter (KIO1 or KIO3), also ensure that a fully wired patch cable is used for the connection between the MultiSensor and the power adapter.