Order-Codes:
Types | KPMDU-RC-4800C13C19-2-16 | KPMDU-RC-4800C13C19-2-32 |
---|---|---|
Rated power, voltage | 2x 3.6kVA, 230V | 2x 7.3kVA, 230V |
Connector plug | 2x CEE-plug(BLUE) according to IEC60309, 1-pole, 16A/230/400V | 2x CEE-plug(BLUE) according to IEC60309, 1-pole, 32A/230/400V |
Connection cable | 2x length 3m, rubber sheathed cableH07RN-F-5G6 | 2x length 3m, rubber sheathed cableH07RN-F-5G6 |
Sockets C13 (IEC60320) | 48 | 48 |
Sockets C19 (IEC60320) | 0 | 0 |
Locking sockets | IEC-LOCK for C13/C19 | |
Fuse circuit breaker | 6 x 10A C-type, 6kA short circuit current, interlocked | 6 x 16A C-type, 6kA short-circuit current, interlocked |
Current measurement (calibrated) | Integrated, calibrated current measurement, accuracy Class B (MID, EN 50470-3) Minimum current 250mA, maximum current 32A | |
Residual current measurement (RCM) | Integrated AC/DC sensitive residual current measurement according to IEC 60664-1 ±300mA/100mA (RMS), Accuracy <0.2mA Frequency range DC 0..2kHz | |
Connectivity | Ethernet (10/100MBit), PoE Class 3 | |
Kentix system socket (type B) | RJ45 with Kentix specific pinout for system expansion 2 x digital input (e.g. Door contacts, leakage detector, ext. alarms) 1 x System BUS | |
Communication and security | HTTPS (certificate), integrated web server, ReSt API Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS, MODBUS-TCP | |
Management | Main satellite management via KentixONE | |
Measurement/communication objects | Voltage (V) L1/L2/L3/Total Current (A) L1/L2/L3/Total Consumption (kWh) L1/L2/L3/Total Active power (W) L1/L2L3/total Apparent power (VA) L1/L2/L3/total Reactive power (VAR) L1/L2/L3/total Effective factor (cos phi) Frequency (Hz) Phase monitoring L1/L2/L3 Differential current AC Differential current DC Fuse status L1/L2/L3 Temperature (°C) Relative humidity (%) Dew point (°C) Vibration (G) Air quality VOC (AIQ Index) | |
Display (LCD) | Illuminated LCD display (power, current, voltage, consumption) | |
Optical signaling | LED with RED/GREEN (operation, alarm/error status) | |
Acoustic signaling | Signal generator with 80dB, 2.3kHz (alarm/fault conditions) | |
Factory state | Button for factory reset(default IP: 192.168.100.226) | |
Power dissipation | max. 40W (full load) | |
Housing | Sheet metal, powder-coated RAL9005, protection class 1, protection rating IP20, mounting bracket with 5U spacing mountable | |
Size | 1770 x 78.2 x 62.5 mm (HxWxD) | |
Weight | approx. 10,5kg | |
Environmental conditions | 0°C to 60°C, humidity 5-95%, storage temperature: -20°C to 60°C | |
Certification | CE (2014/30/EC, 2014/35/EC, 2011/65/EU) | |
Electrical safety | DGUV-V3 testing, VDE 0105-100 | |
Marking | Serial number (barcode), additional free marking area front panel (60x30mm) | |
Scope of delivery | SmartPDU with connection cable 3m and plug, mounting material: 3 90° angle brackets, 12 pieces Countersunk head screws M3x15 with hexagon socket 2mm, test report |