Types | KPMDU-RC-2406C13C19-1-32 | KPMDU- RC-4800C13C19-1-32 | KPMDU-RC- 2406C13C19-1-16 | KPMDU-RC-4800C13C19-1- 16 |
---|---|---|---|---|
Rated power, voltage | up to 7,3kVA, 230V | up to 7,3kVA, 230V | up to 3,6kVA, 230V | up to 3,6kVA, 230V |
Connector plug | CEE plug(BLUE) according to IEC60309, 1-pole, 32A/230V | CEE plug(BLUE) according to IEC60309, 1-pole, 32A/230V | CEE plug(BLUE) according to IEC60309, 1-pole, 16A/230V | CEE plug(BLUE) according to IEC60309, 1-pole, 16A/230V |
Connection cable | Length 3m, rubber sheathed cable H07RN-F-3G6 | Length 3m, rubber sheathed cable H07RN-F-3G6 | Length 3m, rubber sheathed cable H07RN-F-3G2.5 | Length 3m, rubber sheathed cable H07RN-F-3G2.5 |
Sockets C13 (IEC60320) | 24 | 48 | 24 | 48 |
Sockets C19 (IEC60320) | 6 | 0 | 6 | 0 |
Locking sockets | IEC-LOCK for C13/C19 | |||
Fuse circuit breaker with hinged cover (rated current, characteristic, short-circuit current) | 6x 16A C-type, 6kA | 6x 16A C-type, 6kA | 3x 10A C type, 6kA 3x 16A C type, 6kA | 6x 10A C type, 6kA |
Current measurement (calibrated) | Integrated, calibrated current measurement, accuracy Class B (MID, EN 50470-3) Minimum current 250mA, maximum current 32A | |||
Residual current measurement (RCM) | Integrated AC/DC sensitive residual current measurement according to IEC 60664-1 ±300mA/100mA (RMS), accuracy <0.2mA Frequency range DC 0..2kHz | |||
Type 3 overvoltage protection (optional) | Transverse longitudinal voltage protection according to IEC 61643-11 Pluggable protection modules, discharge capacity per pole: In= 5 kA; Imax= 15 kA Monitored by KentixONE, AC mains form: TN ART: KPMDU-xxSD-xxxxC13C19-x-x | |||
Connectivity | Ethernet (10/100MBit), PoE Class 3 | |||
Kentix system socket (type B) | RJ45 with Kentix specific pinout for system expansion 2 x digital input (e.g. door contacts, leakage detector, ext. alarms) 1 x System BUS | |||
Communication and security | HTTPS (certificate), integrated web server, ReSt API Protocols: SNMP V2/3 (GET, TRAP), NTP, SMTP, DHCP, DNS, MODBUS-TCP | |||
Management | Main satellite management via KentixONE | |||
Measurement/communication objects | Voltage (V) L1/L2/L3/Total Current (A) L1/L2/L3/Total Consumption (kWh) L1/L2/L3/Total Active power (W) L1/L2L3/total Apparent power (VA) L1/L2/L3/total Reactive power (VAR) L1/L2/L3/Total Effective factor (cos phi) Frequency (Hz) Phase monitoring L1/L2/L3 Differential current AC Differential current DC Fuse status L1/L2/L3 Temperature (°C) Relative humidity (%) Dew point (°C) Vibration (G) Air quality VOC (AIQ Index) | |||
Display (LCD) | Illuminated LCD display (power, current, voltage, consumption) | |||
Optical signaling | LED with RED/GREEN (operation, alarm/error status) | |||
Acoustic signaling | Signal generator with 80dB, 2.3kHz (alarm/fault conditions) | |||
Factory state | Button for factory reset(default IP: 192.168.100.226) | |||
Power dissipation | max. 40W (full load) | |||
Housing | Sheet metal, powder coated RAL9005, protection class 1, protection class IP20, mounting bracket can be mounted at a distance of 5U | |||
Size | 1770 x 78.2 x 62.5 mm (HxWxD) | |||
Weight | approx. 10,5kg | |||
Environmental conditions | 0°C to 60°C, humidity 5-95%, storage temperature: -20°C to 60°C | |||
Certification | CE (2014/30/EC, 2014/35/EC, 2011/65/EU) | |||
Electrical safety | DGUV-V3 testing, VDE 0105-100 | |||
Marking | Serial number (barcode), additional free marking area front panel (60x30mm) | |||
Scope of delivery | SmartPDU with connection cable 3m and plug, mounting material: 3 pieces 90° angle bracket, 12 pcs. countersunk head screws M3x15 with hexagon socket 2mm, test report |