Order-Codes:
| Function | Extension module for connecting up to 8 differential or 16 single-ended analog inputs |
| Connection optionsöpossibility | Log4J |
| Configuration | Integr. Web server (HTTP) Default IP: 192.168.255.1 |
| Protocols | Modbus TCP / Modbus UDP / MQTT / SNMP v2c |
| Security | ID, password and IP filter |
| Connection terminals | Pluggable spring terminals for cables up to 1 mm² |
| Enteränge | Channels: 8 differential or 16 single-ended analog inputs Type: voltage or current, selectable via DIP switch Measuring ranges per channel (voltage): ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V Measuring ranges per channel (current):0-20 mA, 4-20 mA, ±20 mA Resolution: 16 bit Accuracy: ±0.1 % FSR (Full Scale Range) Sampling rate: normal mode 20 Hz (for all channels), fast mode 200 Hz (for all channels) |
| External sensors | Analog sensors with: Voltage output ±10 V (default) Current output ±20 mA (must be activated by jumper) |
| Insulation | I/O isolation: 3000 V DC |
| Environment | Operating temperature: -25 to +75 °C Humidity: 10 to 90 % RH, non-condensing |
| Network | 2x RJ45, LAN 10/100 Base-TX |
| Power supply | PoE (Class 1) or external power supply unit 10-48VDC, 3.5W |
| Housing | 33 x 127 x 117 mm (DIN rail mounting) |
| Scope of delivery | KIO2217, 3m patch cable, instructions |
| Certification | CE, RoHS-compliant |
| Accessories | Power supply unit or PoE injector if no PoE supply is available |
Terminal assignment

Wiring