{"id":578,"date":"2023-01-08T15:33:47","date_gmt":"2023-01-08T14:33:47","guid":{"rendered":"https:\/\/docs2.kentix.com\/?post_type=ht_kb&#038;p=578"},"modified":"2024-07-17T11:12:41","modified_gmt":"2024-07-17T09:12:41","slug":"multisensor-thermal-image-art-kms-ti-90-b-w","status":"publish","type":"ht_kb","link":"https:\/\/docs.kentix.com\/de\/knowledge-base\/multisensor-thermal-image-art-kms-ti-90-b-w\/","title":{"rendered":"MultiSensor-Thermal Image &#8211; DATENBLATT"},"content":{"rendered":"\n<figure class=\"wp-block-table\"><table><tbody><tr><td><strong>Funktion<\/strong><\/td><td>MultiSensor zur Brandfr\u00fchesterkennung und Raum-\/Fl\u00e4chen\u00fcberwachung<\/td><\/tr><tr><td><strong><strong><strong>Integrierte Software<\/strong><\/strong><\/strong><\/td><td>KentixONE \u00fcber integrierten Web-Server (HTTPS)<\/td><\/tr><tr><td><strong>Sensor &#8211; Lufttemperatur<\/strong><\/td><td>Messbereich -40 bis 85\u00b0C (Genauigkeit \u00b1 0,5\u00b0C)<\/td><\/tr><tr><td><strong>Sensor &#8211; Relative Luftfeuchte<\/strong><\/td><td>Messbereich 0 bis 100% (Genauigkeit \u00b13%)<\/td><\/tr><tr><td><strong>Sensor &#8211; Taupunkt<\/strong><\/td><td>in \u00b0C berechnet<\/td><\/tr><tr><td><strong>Sensor &#8211; Oberfl\u00e4chentemperatur<\/strong><\/td><td>1024 Pixel Infrarot Array mit Germaniumglas Optik, Messbereich -40 bis 1.000\u00b0C, Erfassungskegel je nach Typ: 40\u00b0 oder 90\u00b0, Reichweite bis ca. 5m, Messung: Temperaturbild (32&#215;32), Bewegung<br>NETD (Noise Equivalent Temperature Difference): ca. 150mK\/1Hz<\/td><\/tr><tr><td><strong>Sensor &#8211; Vibration<\/strong><\/td><td>3-Achs Beschleunigungssensor mit Lageerkennung (Empfindlichkeit einstellbar), Messbereich 0.25-5G<\/td><\/tr><tr><td><strong>Sensor &#8211; Kohlenmonoxid (CO)<\/strong><\/td><td>0-1.000ppm Messung \u00b1 10%, Interne Aufl\u00f6sung: 20-1.000ppm (0-100%), Lebensdauer 10 Jahre<\/td><\/tr><tr><td><strong>Sensor &#8211; Luftqualit\u00e4t (VOC, CO2)<\/strong><\/td><td>Messung nach IAQ (Index for Air Quality), IAQ Wert 0-500 entsprechend IAQ Tabelle*<\/td><\/tr><tr><td><strong>Signalgeber<\/strong><\/td><td>85dB, 2.3kHz<\/td><\/tr><tr><td><strong>Externe Alarmeing\u00e4nge<\/strong><br>(KENTIX Systembuchse)<\/td><td>2x Alarm Eingang (z.B. Scharf-Aktiv, Dauer-Aktiv Alarmierung), Beschaltung mit potentialfreien Kontakten \u00fcber separaten KIO3 IO-Adapter<\/td><\/tr><tr><td><strong>Externe Meldeausg\u00e4nge<\/strong><br>(KENTIX Systembuchse)<\/td><td>2x Meldeausgang (z.B. Scharf-Aktiver Alarm, Dauer-Aktiver Alarm), Beschaltung \u00fcber separaten KIO3 IO-Adapter mit Relais Ausg\u00e4ngen<\/td><\/tr><tr><td><strong>LED<\/strong><\/td><td>ALARM (Rot), RUN (Gr\u00fcn), LINK\/ACT an LAN Buchse<\/td><\/tr><tr><td><strong>Ethernet mit PoE<\/strong><\/td><td>10\/100Mbit (Default-IP: 192.168.100.222)<br>Spannungsversorgung \u00fcber PoE Class 2, Leistungsaufnahme ca. 3W<\/td><\/tr><tr><td><strong>Funk (BLE 2.4GHz)<\/strong><br>(nach Ausf\u00fchrung)<\/td><td>2,4GHz ISM Band (BLE), Verschl\u00fcsselung 128Bit<\/td><\/tr><tr><td><strong>SD Karte<\/strong><\/td><td>Integrierter Micro SD Kartenhalter als zus\u00e4tzlicher Speicher f\u00fcr Bildaufzeichnung, bis 128 GB<\/td><\/tr><tr><td><strong>SNMP<\/strong><\/td><td>SNMP V2\/3 (Schreiben\/Lesen), SNMP Traps (Simple Network Management Protocol)<\/td><\/tr><tr><td><strong>ReST API<\/strong><\/td><td>ReST API mit JSON Objekten (HTTPS), Webhooks<\/td><\/tr><tr><td><strong>Geh\u00e4use<\/strong><\/td><td>Material: PS 90 x 90 x 45 mm Gewicht ca. 100g<br>Farben: Wei\u00df, Schwarz<\/td><\/tr><tr><td><strong>Umgebungsbedingungen<\/strong><\/td><td>Temperatur 0 &#8211; 50\u00b0C, Luftfeuchte 5-95%, nicht kondensierend<\/td><\/tr><tr><td><strong>Ausf\u00fchrungen<\/strong><\/td><td>KMS-TI-40-B-BLE (Geh\u00e4use Schwarz, 40\u00b0 Optik)<br>KMS-TI-40-W-BLE  (Geh\u00e4use Wei\u00df, 40\u00b0 Optik)<br>KMS-TI-90-B-BLE  (Geh\u00e4use Schwarz, 90\u00b0 Optik)<br>KMS-TI-90-W-BLE  (Geh\u00e4use Wei\u00df, 90\u00b0 Optik)<br>KMS-TI-40-B (Geh\u00e4use Schwarz, 40\u00b0 Optik)<br>KMS-TI-40-W (Geh\u00e4use Wei\u00df, 40\u00b0 Optik)<br>KMS-TI-90-B (Geh\u00e4use Schwarz, 90\u00b0 Optik)<br>KMS-TI-90-W (Geh\u00e4use Wei\u00df, 90\u00b0 Optik)<\/td><\/tr><tr><td><strong>Lieferumfang<\/strong><\/td><td>Montagehalter, Montagematerial, SlimLine-Kabel 3m<\/td><\/tr><tr><td><strong>Zubeh\u00f6r<\/strong><\/td><td>PoE Injektor (KPOE150S)<br>IO-Adapter (KIO3)<br>Leckagesensor (KLS03)<\/td><\/tr><tr><td><strong><strong><strong>Zertifizierung<\/strong><\/strong><\/strong><\/td><td>CE<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\"><strong>Sichtfeld Thermalbild-Sensor<\/strong><\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">40\u00b0 Optik (ART: KMS-TI-40-x-x)<\/h3>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th class=\"has-text-align-center\" data-align=\"center\">Messabstand<\/th><th class=\"has-text-align-center\" data-align=\"center\">Fl\u00e4che<\/th><th class=\"has-text-align-center\" data-align=\"center\">Messraster<\/th><\/tr><\/thead><tbody><tr><td class=\"has-text-align-center\" data-align=\"center\">1m<\/td><td class=\"has-text-align-center\" data-align=\"center\">73 x 73cm (0,53qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">2,27 x 2,27cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">2m<\/td><td class=\"has-text-align-center\" data-align=\"center\">145 x 145cm (2,12qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">4,55 x 4,55cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">3m<\/td><td class=\"has-text-align-center\" data-align=\"center\">218 x 218cm (4,55qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">6,82 x 6,82cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">4m<\/td><td class=\"has-text-align-center\" data-align=\"center\">291 x 291cm (9,10qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">9,10 x 9,10cm<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\">90\u00b0 Optik (ART: KMS-TI-90-x-x)<\/h3>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><thead><tr><th class=\"has-text-align-center\" data-align=\"center\">Messabstand<\/th><th class=\"has-text-align-center\" data-align=\"center\">Fl\u00e4che<\/th><th class=\"has-text-align-center\" data-align=\"center\">Messraster<\/th><\/tr><\/thead><tbody><tr><td class=\"has-text-align-center\" data-align=\"center\">1m<\/td><td class=\"has-text-align-center\" data-align=\"center\">200 x 200cm (4,00qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">6,25 x 6,25cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">2m<\/td><td class=\"has-text-align-center\" data-align=\"center\">400 x 400cm (16,00qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">12,50 x 12,50cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">3m<\/td><td class=\"has-text-align-center\" data-align=\"center\">600 x 600cm (36,00qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">18,75 x 18,75cm<\/td><\/tr><tr><td class=\"has-text-align-center\" data-align=\"center\">4m<\/td><td class=\"has-text-align-center\" data-align=\"center\">800 x 800cm (64,00qm)<\/td><td class=\"has-text-align-center\" data-align=\"center\">25,00 x 25,00cm<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\"><strong>Messung der Luftqualit\u00e4t nach IAQ Index*<\/strong><\/h2>\n\n\n\n<figure class=\"wp-block-table is-style-regular\"><table><tbody><tr><td><strong>Luftindex<\/strong><\/td><td><strong>Luftqualit\u00e4t<\/strong><\/td><td><strong>Auswirkungen (Langzeit-Exposition)<\/strong><\/td><td><strong>Vorgeschlagene Ma\u00dfnahme<\/strong><\/td><\/tr><tr><td><strong>0<\/strong> <strong>\u2013<\/strong> <strong>50<\/strong><\/td><td>Ausgezeichnet<\/td><td>Reine Luft; das Beste f\u00fcr das Wohlbefinden<\/td><td>Keine Ma\u00dfnahmen erforderlich<\/td><\/tr><tr><td><strong>51<\/strong> <strong>\u2013<\/strong> <strong>100<\/strong><\/td><td>Gut<\/td><td>Keine Irritationen oder Auswirkungen auf das Wohlbefinden<\/td><td>Keine Ma\u00dfnahmen erforderlich<\/td><\/tr><tr><td><strong>101<\/strong> <strong>\u2013<\/strong> <strong>150<\/strong><\/td><td>Leicht verschmutzt<\/td><td>Reduzierung des Wohlbefindens m\u00f6glich<\/td><td>Bel\u00fcftung vorgeschlagen<\/td><\/tr><tr><td><strong>151<\/strong> <strong>\u2013<\/strong> <strong>200<\/strong><\/td><td>M\u00e4\u00dfig verschmutzt<\/td><td>Deutlichere Irritation m\u00f6glich<\/td><td>Erh\u00f6hen Sie die Bel\u00fcftung mit sauberer Luft<\/td><\/tr><tr><td><strong>201<\/strong> <strong>\u2013<\/strong> <strong>250<\/strong><\/td><td>Stark verschmutzt<\/td><td>Die Exposition kann je nach Art der VOCs zu Auswirkungen wie Kopfschmerzen f\u00fchren<\/td><td>Bel\u00fcftung verbessern<\/td><\/tr><tr><td><strong>251<\/strong> <strong>\u2013<\/strong> <strong>350<\/strong><\/td><td>Stark verschmutzt<\/td><td>Schwerwiegendere Gesundheitsprobleme m\u00f6glich, wenn sch\u00e4dliche VOC vorhanden sind<\/td><td>Kontamination sollte identifiziert werden, wenn das Niveau auch ohne Anwesenheit von Personen erreicht wird; Bel\u00fcftung maximieren &amp; Anwesenheit reduzieren<\/td><\/tr><tr><td><strong>&gt; 351<\/strong><\/td><td>Extrem verschmutzt<\/td><td>Kopfschmerzen, zus\u00e4tzliche neurotoxische Effekte m\u00f6glich<\/td><td>Kontaminationen m\u00fcssen identifiziert werden; Anwesenheit im Raum vermeiden und Bel\u00fcftung maximieren<\/td><\/tr><\/tbody><\/table><\/figure>\n","protected":false},"excerpt":{"rendered":"<p>Funktion MultiSensor zur Brandfr\u00fchesterkennung und Raum-\/Fl\u00e4chen\u00fcberwachung Integrierte Software KentixONE \u00fcber integrierten Web-Server (HTTPS) Sensor &#8211; Lufttemperatur Messbereich -40 bis 85\u00b0C (Genauigkeit \u00b1 0,5\u00b0C) Sensor &#8211; Relative Luftfeuchte Messbereich 0 bis 100% (Genauigkeit \u00b13%) Sensor &#8211; Taupunkt in \u00b0C berechnet Sensor &#8211; Oberfl\u00e4chentemperatur 1024 Pixel Infrarot Array mit Germaniumglas Optik, Messbereich&#8230;<\/p>\n","protected":false},"author":2,"featured_media":579,"comment_status":"open","ping_status":"closed","template":"","format":"standard","meta":{"_crdt_document":"","inline_featured_image":false,"footnotes":""},"ht-kb-category":[73,63],"ht-kb-tag":[],"class_list":["post-578","ht_kb","type-ht_kb","status-publish","format-standard","has-post-thumbnail","hentry","ht_kb_category-datenblaetter","ht_kb_category-datenblaetter-smartmonitoring"],"custom_fields":{"kentix_order_code":["KMS-TI-90-B,KMS-TI-90-W,KMS-TI-90-B-BLE,KMS-TI-90-W-BLE,KMS-TI-40-B,KMS-TI-40-W,KMS-TI-40-B-BLE,KMS-TI-40-W-BLE"]},"categories":[{"slug":"datenblaetter","name":"Datenbl\u00e4tter Hardware","shortName":""},{"slug":"datenblaetter-smartmonitoring","name":"Datenbl\u00e4tter","shortName":""}],"featured_media_url":"https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/01\/343617_KMS-TI-B-front-1-150x113.png","_links":{"self":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/578","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb"}],"about":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/types\/ht_kb"}],"author":[{"embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/comments?post=578"}],"version-history":[{"count":37,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/578\/revisions"}],"predecessor-version":[{"id":10020,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/578\/revisions\/10020"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/media\/579"}],"wp:attachment":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/media?parent=578"}],"wp:term":[{"taxonomy":"ht_kb_category","embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb-category?post=578"},{"taxonomy":"ht_kb_tag","embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb-tag?post=578"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}