{"id":3446,"date":"2023-03-14T13:53:51","date_gmt":"2023-03-14T12:53:51","guid":{"rendered":"https:\/\/docs2.kentix.com\/?post_type=ht_kb&#038;p=3446"},"modified":"2026-03-05T14:27:02","modified_gmt":"2026-03-05T13:27:02","slug":"faq-warum-kommt-es-zu-fehlausloesungen-durch-den-leckagesensor","status":"publish","type":"ht_kb","link":"https:\/\/docs.kentix.com\/de\/knowledge-base\/faq-warum-kommt-es-zu-fehlausloesungen-durch-den-leckagesensor\/","title":{"rendered":"Warum kommt es zu Fehlausl\u00f6sungen durch den Leckagesensor?"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">Der Kentix Leckagesensor KLS03 meldet seinen Alarm \u00fcber den digitalen Eingang am AlarmManager oder einem MultiSensor. Bei Fehlerhaften Alarmen pr\u00fcfen sie bitte folgende Punkte.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Dauerhafte Alarmierung<\/h2>\n\n\n\n<h3 class=\"wp-block-heading\">Schaltlogik<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Da sich dieser Eingang ohne eine Beschaltung durch externe Komponenten in ge\u00f6ffnetem Zustand befindet, der Leckagesensor diesen Eingang beim Einstecken jedoch schlie\u00dft, wird nach dem Anschluss an diesem Eingang ein anstehender Alarm signalisiert.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Stellen sie den den Systemeingang 1 am AlarmManager deshalb nach Verbinden des Leckagesensors auf \u201cAlarm wenn \u2013 Offen\u201d<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Sie k\u00f6nnen jetzt mit Hilfe eines feuchten Tuches die Alarmierung durch den Leckagesensor testen.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Besch\u00e4digung<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Erfolgen Alarme nach der Umschaltung der Logik weiter, \u00fcberpr\u00fcfen sie die Sensorfl\u00e4che auf Sauberkeit und Korrosion. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Die Erkennung von Leckagen erfolgt durch das Prinzip der elektrischen Leitf\u00e4higkeit von Wasser.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Ist die Sensorfl\u00e4che mit Partikeln behaftet oder Korrodiert, kann dadurch ein dauerhafter Alarm entstehen.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Ausbleibende Alarmierung<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Der Alarm f\u00fcr den Leckagesensor muss &#8222;Dauer-Aktiv&#8220; geschaltet sein, damit er nicht durch eine m\u00f6gliche Umschaltung der Scharfschaltung der Alarmgruppe unterdr\u00fcckt wird.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Leckagesensor Rope<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">Der Leckagesensor Rope l\u00f6st erst dann einen Alarm aus, wenn auf insgesamt 20cm L\u00e4nge ca. 10ml Wasser gemessen werden. Es ist dabei unerheblich, ob die Wassermenge an einem St\u00fcck oder an verschiedenen Stellen des Sensors anliegt. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Zum Testen der Funktion ist es m\u00f6glich einen nassen Lappen um das Messkabel herum zu wickeln und so einen Alarm auszul\u00f6sen.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img loading=\"lazy\" decoding=\"async\" width=\"760\" height=\"330\" src=\"https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered.jpeg\" alt=\"\" class=\"wp-image-3447\" srcset=\"https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered.jpeg 760w, https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered-400x174.jpeg 400w, https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered-150x65.jpeg 150w, https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered-50x22.jpeg 50w, https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered-60x26.jpeg 60w, https:\/\/docs.kentix.com\/wp-content\/uploads\/2023\/03\/rope_alarm_triggered-100x43.jpeg 100w\" sizes=\"auto, (max-width: 760px) 100vw, 760px\" \/><\/figure>\n","protected":false},"excerpt":{"rendered":"<p>Der Kentix Leckagesensor KLS03 meldet seinen Alarm \u00fcber den digitalen Eingang am AlarmManager oder einem MultiSensor. Bei Fehlerhaften Alarmen pr\u00fcfen sie bitte folgende Punkte. Dauerhafte Alarmierung Schaltlogik Da sich dieser Eingang ohne eine Beschaltung durch externe Komponenten in ge\u00f6ffnetem Zustand befindet, der Leckagesensor diesen Eingang beim Einstecken jedoch schlie\u00dft, wird&#8230;<\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"closed","template":"","format":"standard","meta":{"_crdt_document":"","inline_featured_image":false,"footnotes":""},"ht-kb-category":[62],"ht-kb-tag":[],"class_list":["post-3446","ht_kb","type-ht_kb","status-publish","format-standard","hentry","ht_kb_category-faq-smartmonitoring"],"custom_fields":{"copied_media_ids":["a:1:{i:0;i:3447;}"],"referenced_media_ids":["a:0:{}"],"kentix_order_code":["KLS03"]},"categories":[{"slug":"faq-smartmonitoring","name":"FAQ","shortName":"FAQ"}],"featured_media_url":null,"_links":{"self":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/3446","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb"}],"about":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/types\/ht_kb"}],"author":[{"embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/comments?post=3446"}],"version-history":[{"count":5,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/3446\/revisions"}],"predecessor-version":[{"id":12872,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb\/3446\/revisions\/12872"}],"wp:attachment":[{"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/media?parent=3446"}],"wp:term":[{"taxonomy":"ht_kb_category","embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb-category?post=3446"},{"taxonomy":"ht_kb_tag","embeddable":true,"href":"https:\/\/docs.kentix.com\/de\/wp-json\/wp\/v2\/ht-kb-tag?post=3446"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}